The ADC371 is our rate of change signal input signal transmitter suitable for SIL 1, 2 & 3 applications
- Input is any DC current or voltage can be specified in the range of 100mA max; Voltage up to 150V max
- Output is a signal proportional to the input Rate of Change
- The rate of change is controlled by a 15 turn potentiometer
Environmental Condition
Performance
Mounting/Dimensions
Environmental Condition
Storage Temperature: -40°C to +70°C
Operating Ambient: -15°C to +55°C
Relative Humidity 5% to 95% RH
Performance
Response time: Typically <1 Sec
Accuracy: <±0.5% span
Supply regulation: DC ±10%, AC ±20%
Supply consumption: <3VA
Mounting/Dimensions
Enclosure: 50w x 75h x 110d mm
Din Rail (TS35) or Surface by corner fixing holes