The AHM710 is our millivolt input trip signal transmitter which is suitable for SIL 1, 2 & 3 rated (EN 61508-2) safety system loop applications
- Input to accept mV signal from thermocouple Type S, R, B, J, K, T, E, N and other special types also available on request.
- Output DC current or voltage specified in ranges seen on datasheet
Environmental Condition
Performance
Mounting/Dimensions
Environmental Condition
Storage Temperature: -40°C to +70°C
Operating Ambient: -15°C to +55°C
Relative Humidity: 5% to 95% RH (Non-Condensing)
Performance
Response time: <400mS (0-100% input step change)
Accuracy/Linearity : ±0.1% mV span
Mounting/Dimensions
Card 3U high 4E wide
Mounting 19″ rack / 84E wide (See rack GA for details)
Card weight <200g