Our AGS1119RX-4-2X is a Four Channel RTD Input Temperature Trip Amplifier which is suitable for combinations of temperature process inputs and SIL1 & SIL 2 rated (EN 61508-2) safety instrumented system (SIS) loop applications, as 1oo1 architecture (HFT:0).
- Input is any 2/3 wire PT100 or PT1000 RTD type & temperature ranges may be specified
- Relay Outputs; Common High-High Temperature Trip output, DPCO Contacts, individual channel High temperature Alarm output.
- Alarm & Trip Functions; High temperature alarm & High-High temperature trip set points for each input channel, all independently adjustable over the full input temperature range. Four amber Alarm LED’s, one for each input channel.
Environmental Condition
Performance
Mounting/Dimensions
Environmental Condition
Storage Temperature: -40°C to +70°C
Operating Ambient: -15°C to +55°C
Relative Humidity: 5% to 95% RH (Non Condensing)
Performance
Trip settability: ±1%
Trip repeatability: ±0.1%
Response time: <400mS
Input O/C response: Upscale drive
Mounting/Dimensions
Enclosure: 152w x 137h x 81d mm
Mounting: Din Rail (TS35)