Our ADC311DI is a Process Signal Scale & Bias Input Transmitter with continuous indication of output signal on front fascia digital display, which is suitable for SIL 1 & SIL2 rated (EN 61508-2) safety instrumented system (SIS) loop applications, as 1oo1 architecture.
- Input; Any voltage or current signal (DC) that can be terminated in a PI network to produce a 400mV span. Current ranges up to 100mA max input, Voltage ranges up to 250Vdc max input.
- Output; Any standard process current or voltage in the range of; Current source up to 22mA max, with drive voltage 24Vdc, Voltage source up to 20V max output. Continuous indication of output signal on front fascia digital display
Environmental Condition
Performance
Mounting/Dimensions
Environmental Condition
Storage Temperature: -40°C to +70°C
Operating Ambient: -15°C to +55°C
Relative Humidity: 5% to 95% RH (Non-Condensing)
Performance
Accuracy/Linearity: <±0.1%
Response time: <100mS (0-100% input step change)
Supply consumption: <3VA
Mounting/Dimensions
Enclosure: 50w x 75h x 145d mm
Mounting: Din Rail (TS35) or Surface by corner fixing holes (front of panel option available)